This project consists of work at: MC Medical Examiner, 43585 Elizabeth Road, Mt. Clemens MI 48043.
A. The project consists of all necessary prep, labor and material to perform the indicated work to fully install an operational full body x-ray machine:
1. Provide new 112.5 kva 208-480/277v step up transformer located within the facility.
2. Provide new 480v/100AS/100AF disconnect for the new x-ray machine.
3. Provide new 70A 480V enclosed circuit breaker w/shunt trip with connection to the existing generator.
4. Provide new 400A non-fused service disconnect on the existing generator.
5. Provide conduit, boxes, wiring, devices.,etc.. as shown on the drawings and/or as required to complete the installation of the x-ray machine so it is fully functional.
6. Firestopping and fire sealing of all penetrations in existing floors/walls is required.
7. An alternate is being solicited to provide a new 225 breaker in the existing 1200A Main Distribution Panel.