Specifications include, but are not limited to: Group A – Steel Structures General – Provide all necessary structural steel as shown on Specification Drawings and as described in Steel Specification Group A – Insulators 115kV Station Post Insulators Quantity............................................. Nine (9) Manufacture......................................Victor ASA................................................... TR286 Strength ............................................Standard Type..................................................Station Post, 5” B.C.; Provide all necessary bus conductors, connectors, and other materials required to completely interconnect power equipment as shown on specification drawings. This includes all bus connectors, bus splicing material, bolts, nuts, washers, etc. Type, size and quality of major bus materials is defined in schedule form on the Material list. The intent of that schedule is to set a quality standard for bus and equipment as well as to specify other necessary requirements.;Bus Conductor 12 A minimum number of conductor types and sizes have been included in the design of electrical bus in this section. All sections of tubular conductor longer than eight feet between supports require damping conductors. Damping conductor shall be furnished as specified on the following table. Tubular bus conductor shall be Schedule 40 seamless electrical grade 6063-T6. All bus work shall have smooth surface Industry Class IV finish. Care shall be exercised in handling and packaging for shipment, all bus conductors to prevent abrasion or other damage.