Specifications include, but are not limited to: a). Complete elemental water analysis for Boiler(s), raw water and make-up & feed water as needed. b). Deposit analysis Boiler waterside as needed. c). Corrosion coupon analysis for boilers Feed Water & Condensate if requested. d). Metallographic analysis as needed for specific problems. e). Zeolite resin analysis as needed for specific problems. f). Fuel oil testing Minimum once per year – Calorific value, viscosity, bacteria, bottom water, sediment g). Boroscope inspection as needed for specific problems h). Oxygen level Deaerator, as needed for a specific problem i). Amine studies as needed for specific problems j). Steam quality studies as needed for specific problems k). In house membrane autopsy with written report as needed for specific problems