Conform to the requirements specified herein for the type and class of material named. The Engineer reserves the right to reject any materials not meeting these Specifications. See ‘Form A: Price Proposal’ for associated bid quantities and the Bid Form worksheet. Material Requirements – HYDRANTS: Acceptable models: − AFC Waterous Pacer WB-67 In addition, they must meet the following requirements: − All hydrants shall be “breakaway.” − 5” valve opening − One piece hydrant barrel − Center line of nozzles shall be designed for minimum of 17” above ground level − (2) 2 ½” side nozzles − (1) 4 ½” pumper nozzle − 6” mechanical joint bottom connection to mechanical joint pipe with conductive M.J. (no lead) gasket and necessary accessories − Hydrant open left − National Standard threads and operating nut shape − Paint: Red with blue nozzle caps. Waterous color M4152 (Houston Blue), or equal − Caps chained and attached to hydrant − 360 degrees top rotation − Dry top-operating threads to be sealed when opened − Brass to brass foot valve − Upper valve plate to be brass − Bronze shaft sleeve − Plastic drain valve facing (otherwise, drain tube / drain valve assembly) − All specifications to be verified by bidder