UPS system needs to accommodate the following: • System Capacity: 30kVa/27kw 208V 3-phase UPS system. • Input/Output Voltage: 208/120V (3W + N + G) – single or dual feed. • Redundant Internal VRLA Battery Strings - provide 11 minutes of runtime at Full System Load (30kVa), and 35 minutes of runtime at 12 kVa of Load (.9PF). • Include SNMP Communications Card with UPS and external battery cabinet. • Include 1-year parts & labor warranty to include UPS, batteries, 24x7 onsite start up service, PM’s. • Include Tech Support 24x7 Onsite for removal of existing and installation of new UPS. • Include 24x7 onsite startup of UPS by Manufacture. • Include removal and disposal of existing UPS from customer dock. • Include dock to dock shipping. • Provide all spec sheets for UPS to include O&M’s, installation drawings, power requirements. • UPS Manufacturer must have a (EOSL) end of service life grader than 15 years and supported OEM for same period of time from Manufacture date.