Specifications include, but are not limited to: The purchase and installation of a card access system per the specifications. 13.1 Access Card System Control Panels 13.1.1 Access card system control panels must be able to control access to a total of seventy-three (73) doors with a total of one hundred eighteen (118) card readers throughout the hospital's facility. 13.1.2 Access card system control panels must be able to control access to a total of eleven (11) elevator call stations. 13.1.3 Access card system control panels must be able to communicate with the existing Honeywell ProWatch card access system in place at DHHR locations throughout the State. 13.1.4Access card system control panels must be able to communicate with the Honeywell ProWatch servers located at Building 6 in Charleston, WV. 13.2Access Card System Readers 13.2.1Must provide one hundred twenty-nine (129) access card system readers to allow access through various doors and elevators throughout the hospital's facility, as identified in EXHIBIT C. 13.2.2Access card system card readers must be able to communicate with the existing Honeywell ProWatch card access system in place at DHHR locations throughout the State. 13.2.3 Access card system readers must be able to communicate with the item listed in 13.1. 13.3 Door Locks 13.3.1 Magnetic door locks must be installed on thirty (30) doors that has have an access card system reader installed on them. 13.3.2 Magnetic door locks must provide a minimum of one thousand two hundred (1,200) pounds of resistance. 13.3.3 Magnetic door locks must communicate and function accordingly with the card access system. 13.3.4 Electric strikes must be installed on fifty-five (55) doors that have an access card system reader installed on them. 13.3.5 Electric strike must communicate and function accordingly with the card access system. 13.4 Access Cards 13.4.1 Must provide five hundred (500) access cards that will be compatible and function accordingly with the card access system.