Secondary Cable #1/0 Triplex


Location
Washington
Publication Date
09/11/2020 10:54 AM EDT
Closing Date
09/28/2020 06:00 PM EDT
Issuing Organization
Kittitas County Public Utility District
Solicitation Number
Description

Specifications include, but are not limited to: 1. General All underground service cable shall be type USE insulated aluminum conductors suitable for use in wet or dry locations and suitable for direct burial or installation in underground duct. 2. Conductor and Insulation a. Triplexed cables shall have a reduced size neutral consisting of stranded aluminum, insulated with yellow or yellow striped-black cross-linked polyethylene. b. The phase conductors shall be stranded aluminum, insulated with black cross-linked polyethylene. c. Triplexed configuration shall be accomplished by cabling two phase conductors with one neutral conductor. d. The cable shall have a voltage rating of 600 volts phase to phase and conductor operating temperature of 90 C.