Specifications include, but are not limited to: 15KV 600AMP GANG SWITCH COMPARTMENT - The design of the enclosure, bus work, and support insulators shall be such that all support insulators shall be completely visible without switch and/or fuse disassembly, in order to facilitate inspection and cleaning. 2.03.1C.2 – 15KV 200AMP FUSED CABLE COMPARTMENT - DeadFront: The design of the compartment shall be consistent with dead-front operation. Access shall be limited by a self-closing door, aka: shutter barrier, of GPO-3 insulating material, rated for the voltage. The shutter barrier shall be connected with a nonconducting adjustable linkage to the fuse door. LiveFront: The design of the compartment shall be consistent with Live-front operation. Each pole shall include an approved load interrupter that includes provisions for a S&C Loadbuster Tool...