Specifications include, but are not limited to: 1. Inspect physical, electrical and mechanical condition including evidence of moisture or corona. 2. Perform an ultrasonic leak and corona test on all connections using an industry standard detector. The brand and model of the detector must be approved by AlexRenew. 3. Inspect anchorage, alignment, grounding, and required area clearances. 4. Clean transformers and check stress cones. 5. Verify that fuse and/or circuit breaker sizes and types correspond to drawings and coordination study as well as to the circuit breakers' address for microprocessorcommunication packages. 6. Perform an infrared inspection on bolted electrical connections for high resistance. 7. Confirm correct operation and sequencing of electrical and mechanical interlock systems. 8. Use appropriate lubrication on moving current-carrying parts and on moving and sliding surfaces. 9. Verify correct barrier and shutter installation and operation. 10. Exercise all active components.