Specifications include, but are not limited to: 4.1.1. Contractor shall coordinate connection between the server and BMS system 4.1.2. Contractor shall furnish and install 50,000 point SkySpark solution instance on the cloud server through VPN/RDP 4.1.3. Contractor shall Install and configure JVM on the cloud server 4.2.1. Contractor shall furnish and assign BacNet devices (Device IDs and IP Addresses) 4.2.2. Contractor shall login to each BMS, evaluate the origin and purpose of each point through visual identification (graphics). Current labels are generic and not specific. 4.2.3. Contractor shall update each BacNet object name, to a user comprehensible tag in the BacNet system for future repair identification purposes and to streamline communication with solution. 4.2.4. Contractor Shall partner with internal/external customers and PWCS to identify 500 consistent and meaningful points at 23 sites (11,500 points) that will be mapped back to the server. 4.2.5. Contractor shall map each BacNet point into solution using hierarchical identifiers including site, equipment and point.