Install and integrate One (1) 1,000 Gallon product tank. Tank must be a UL 142 double wall tank, primed and painted white and include at a minimum: Universal Vacuum Vent 8 oz. Vac Pressure externed 60” above tank UL Listed Emergency Vents Annular/interstitial space Leak Gauge OPW 200TG Tank Gauge Safety Drum Funnel w/ Self-Closing Cover & Flame Arrester Swing Check Valve UL Listed, FM Approved, NSF/ANSI 61 & 372 Manual Overfill Valve for top loading storage tanks “Flammable” Vinyl decal 3 in. red lettering on white background on all sides “No Smoking” Vinyl Decal 3 in. red lettering on white background on all sides “Drain Sump Daily” decal with quantity at sump location Pipe Markers w/red arrows - 1 in. x 3 in 1203 DOT Flammable Placards on all sides NFPA 704 hazard identification system decals on front of tank Heavy Duty Grounding Reel, 50ft. with cable and clamp Manual sump pump anti-siphon with lockable valve Provide and install all piping and valves to connect the tank and pump (1.5” min.) and pump to hose reel (1”) with stainless steel piping and fittings Parker Velcon VF-61 Filtration Housing w/ Differential Pressure Guage, 5 - 50 GPM Parker/Velcon ACO Series aviation filter 5 in. x 12 in. ACO-51201P 3/4 in. Aviation Fueling Hose w/ MxM NPT Ends Length: 50 ft. Hewitt Osprey S Aviation Over Wing Fueling Nozzle Color: Red All piping will be painted white with direction of flow arrows HANNAY Model V-EPJ6032-19-21 Power Rewind Reel 115V 1" FNPT connections, stainless steel fluid path and C2 roller assembly. One (1) Year workmanship and parts warranty