1. The Contractor shall provide one (1) Flammable Chemical Storage Locker (see Attachment C) which shall have the following specifications: a. Oil and chemical flammable storage locker with loading ramp to be located at the guard shack area. b. Flammable storage locker shall have interior shelving for small chemical storage. c. Drum capacity for flammable storage locker must be a minimum of (16) 55-gallon drums with room for additional shelving. d. Hurricane Rated Construction e. Explosion Proof LED interior lighting f. Lockable swing away or single roll up door to provide forklift loading. g. Sump capacity of approximately 293gal. h. Must meet OSHA, EPA, NFPA30, FM, SMaRT and NFPA 1 regulations. i. UV and Chemical Resistant Paint j. 2 Hour Fire Rated k. Natural Draft Ventilation for dispersal of fumes l. Anchor plates for permanent mounting m. Metal DOT Hazmat placard with aluminum holder n. Manufactured in accordance with ASTM, AISI and AWS materials and fabrication standards. o. Flammable Storage Locker must be colored white. 2. The Contractor shall provide two (2) Fuel Caddies (see Attachment E) with the following key features: a. 30-Gallon capacity steel tank b. UL-Listed, complies with OSHA guidelines c. Fill Level gauge d. Internal filter system e. 4-way directional valve f. 2-way manual pump with carbon vanes and Viton seals g. Heavy-duty locking rear wheel and locking front caster h. Ground wire and clamp i. 8’ PVC suction/discharge hose with internal grounding wire j. Decals set for contents identification k. Red in color l. Front locking swivel casters m. Rear 10” or large Heavy-Duty Tires