Specifications include, but are not limited to: Replacement of Circuit Breaker Panels at 3 Chesterfield County Schools. Three breakers each at Meadowbrook and Matoaca High Schools, and one at Grange Hall Elementary School. MEADOWBROOK HS 1. Panel H1A: Replace the 35 A GE type THED circuit breaker feeding AHU-5 (H1A_AHU-5S) with a type SELA breaker to exceed the short circuit rating of 32.4 kA. 2. Panel EDP3: Remove the GE type TED breakers from panel EDP3 existing since they are not being used. 3. Panel EH1E: Replace the 20 A GE type TEY circuit breaker to meet NEC requirements. MATOACA HS 1. Panel EH1: Install a 125 A Siemens type FXD6 breaker as a subfeed on panel EH1, to power panel EH2. This will significantly improve downstream coordination. Recommend using a 1 AWG cable size for the new breaker feeding panel EH1, to meet NEC requirements for conductor protection. 2. Panel LD1: Replace the circuit breakers in panel LD1 with breakers having a short circuit rating exceeding 11.18 kA. 3. Panel LD2: Replace the circuit breakers in panel LD2 with breakers having a short circuit rating exceeding 11.1 kA. GRANGE HALL ES 1. Panel DPA: Replace the GE type TQD circuit breakers in panel DPA with GE type TED breakers having a short-circuit rating exceeding 13.874 kA.