Specifications include, but are not limited to: • UCA is in need of a 60’ tower that has the available loading capacity for up to three 4’ to 6’ microwave dishes going to downstream communications sites (provided by UCA). These will require either EW90 or EW63 eliptical waveguides (depending on licensing requirements) going from the dishes to the top of racks inside the shelter. All waveguide runs will be secured down the tower face using appropriate waveguide cushions. We will need 3 ground kits on each run of elliptical waveguide (top, base, entry port), weather seal all connectors using self-adhesive material and install entry boots at the entry port. Waveguides will need to be pressure tested to ensure correct installation. UCA will provide the antenna mounts, antennas, ground kits, waveguide hangers, and connectors. Any metallic hardware used outside and especially on the tower will be stainless steel, aluminum, or hot dipped galvanized steel (no electroplated type galvanizing, etc.) • UCA will require at a minimum two to three 7’ equipment racks in the shelter to house our various backhaul equipment. • UCA requires that the shelter be secured with a locking apparatus, weather tight and rodent free with a backup generator and air conditioning with adequate capabilities for backup of UCA equipment. Our minimum standards require a 10KW backup generator and a 2 ½ ton A/C unit. • UCA requires 24x7 access to the site and the road to be reasonably accessible by 4x4 vehicle with the exception of winter months where access would be done by snowcat or other means.