Specifications include, but are not limited to: A. Factory-assembled and -tested, water-cooled engine, with brushless generator and accessories. B. Electrical Components, Devices, and Accessories: Listed and labeled as defined in NFPA 70, by a qualified testing agency, and marked for intended location and application. C. Service Load: 1250 KW /1562 kVA. D. Power Factor: 0.8 Lagging E. Frequency: 60 Hz F. Voltage: 13,200 V ac. G. Phase: Three H. Induction Method: Turbocharged. I. Governor: Adjustable isochronous, with speed sensing. J. Mounting Frame: Structural steel framework to maintain alignment of mounted components without depending on concrete foundation. Provide lifting attachments sized and spaced to prevent deflection of base during lifting and moving. 1. Rigging Diagram: Inscribed on metal plate permanently attached to mounting frame to indicate location and lifting capacity of each lifting attachment and engine generator center of gravity. K. Capacities and Characteristics: 1. Power Output Ratings: Nominal ratings as indicated at 0.8 power factor. 2. Nameplates: For each major system component to identify manufacturer's name, model, and serial number, of component.