Specifications include, but are not limited to: a.The existing concrete slab is approximately 20’x15’ with the structure currentlyhousing the pump station.The contractor will be responsible for the removal of thebuilding and existing slab, and replacement.Minimum requirements for the newpad to fit the pump station is 22’x 14’ consisting of ½” rebar re-enforcement and aminimum of 6” thick concrete.b.Wet Well must consist of a minimum of 6’ diameter x 17’ depth and intake flumeshould consist of 100’ of 24” (or larger) HDPE dual wall pipe or comparable. Intakecapped w/ a minimum of 30”x30”x30” box intake screen consisting of stainlesssteel or comparable.c.Building enclosure recommended to fit pad size and consist of R-13 insulation or equivalent, pump hatch, and adequate venting.d.Installation of new pump station including but not limited to: Crane, Labor, Z-pipeconnection, and electrical connection.