EST. QUANTITY 2 "XFMR 100 KVA 120/240V SINGLE PH SUBMERSIBLE; TRANSFORMER SINGLE PHASE SUBMERSIBLE DISTRIBUTION 1247OY/7200, 120/240V, 95 KV BIL MAX IMPEDANCE 2 PERCENT, 100 KVA. NO TAPS, SUITABLE FOR SUBMERSIBLE OPERATION AND BANKING. TRANSFORMERS SHALL BE EQUIPPED WITH SECONDARY BREAKERS AND PROTECTED WITH A WEAK LINK INTERNAL FUSE IN THE PRIMARY CONNECTION. TRANSFORMERS SHALL BE EQUIPPED WITH TWO 200 AMP LOAD BREAK LOOP FEED INTERNAL PRIMARY SWITCHES ARRANGED SO THAT THE TRANSFORMER MAY BE ENERGIZED FROM EITHER OR BOTH OF THE HIGH VOLTAGE BUSHING. ALL HIGH VOLTAGE, LOW VOLTAGE BUSHINGS AND GROUNDING LUGS SHALL BE CONSTRUCTED AND ATTACHED TO THE COVER IN SUCH A MANNER THAT NO LEAKAGE WILL OCCUR AFTER PRIMARY AND OR SECONDARY CABLES ARE ATTACHED. THE FOUR LOW VOLTAGE INSULATED BUSHINGS SHALL BE LOCATED ON THE COVER IN THE QUADRANT OF THE COVERS OPPOSITE THE PRIMARY BUSHINGS. THE LOW VOLTAGE BUSHINGS SHALL BE STANDARD FOUR HOLE SPADE. A PARKING STAND SHALL BE PROVIDED ON THE COVER BETWEEN THE PRIMARY BUSHINGS. THE PRIMARY BUSHINGS SHALL BE UNIVERSAL BUSHING WELLS AND THE BE FURNISHED WITH ALL COPPER CURRENT CARRYING LOAD BREAK INSERTS. TRANSFORMER OIL SHALL BE NON-PCB, WITH A NON-PCB LABEL PLACED BELOW THE NAMEPLATE. TRANSFORMER SHALL BE MANUFACTURED, TESTED IN ACCORDANCE WITH ANSI C57.12.23 LATEST REVISION. SPECIFICATION E-640. ADDITIONAL PURCHASING DESCRIPTION: PHYSICAL DIMENSIONS OF TRANSFORMER: MAXIMUM HEIGHT SHALL BE 53 INCHES, MEASURED FORM BOTTOM OF THE BASE TO TOP OF THE BUSHING; MAXIMUM DIAMETER SHALL BE 22 INCHES, MEASURED FROM OUTSIDE OF LIFTING ARM ONE SIDE TO OUTSIDE OF LIFTING ARM ON THE OTHER SIDE. IN QPL EL-17"; "XFMR 75 KVA 120/240V SINGLE PH SUBMERSIBLE; TRANSFORMER SINGLE PHASE SUBMERSIBLE DISTRIBUTION 1247Y/7200, 120/240V, 95 KV BIL MAX IMPEDANCE 2 PERCENT 75 KVA. NO TAPS, SUITABLE FOR SUBMERSIBLE OPERATION AND BANKING. TRANSFORMERS SHALL BE EQUIPPED WITH SECONDARY BREAKERS AND PROTECTED WITH A WEAK LINK INTERNAL FUSE IN THE PRIMARY CONNECTION. TRANSFORMERS SHALL BE EQUIPPED WITH TWO 200 AMP LOAD BREAK LOOP FEED INTERNAL PRIMARY SWITCHES ARRANGED SO THAT THE TRANSFORMER MAY BE ENERGIZED FROM EITHER OR BOTH OF THE HIGH VOLTAGE BUSHINGS. ALL HIGH VOLTAGE, LOW VOLTAGE BUSHINGS AND GROUNDING LUGS SHALL BE CONSTRUCTED AND ATTACHED TO THE COVER IN SUCH A MANNER THAT NO LEAKAGE WILL OCCUR AFTER PRIMARY AND OR SECONDARY CABLES ARE ATTACHED. THE FOUR LOW VOLTAGE INSULATED BUSHINGS SHALL BE LOCATED ON THE COVER IN THE QUADRANT OF THE COVERS OPPOSITE THE PRIMARY BUSHINGS. THE LOW VOLTAGE BUSHINGS SHALL BE STANDARD FOUR HOLE SPADE. TWO PARKING STANDS SHALL BE PROVIDED ON THE COVER BETWEEN THE PRIMARY BUSHINGS. THE PRIMARY BUSHINGS SHALL BE UNIVERSAL WELLS AND BE FURNISHED WITH ALL COPPER CURRENT CARRYING LOAD BREAK INSERTS. TRANSFORMER OIL SHALL BE NO-PCB, WITH A NO-PCB LABEL PLACED ON THE SIDE OF THE TANK. TRANSFORMER SHALL BE MANUFACTURED, TESTED IN ACCORDANCE WITH ANSI C57.12.23 LATEST REVISION, AND AE SPECIFICATION DRAWING AE SUBMERSIBLE TRANSFORMER. ALL MAJOR DIMENSIONS WILL BE SHOWN ON THE AE SPECIFICATION DRAWING. IN QPL EL-17"