A. Current Equipment Specifications: 1. Make/Model: Lennox/ LGA102H4BS4Y 2. Serial Numbers: 5608C00496/5608C00497 3. Manufacture Date: 2008 4. Install Date: 2008 5. Size/Ton: 8.5 Ton 6. Refrigerant: American Society of Heating, Refrigerating and Air-Conditioning Engineers (ASHRAE) Refrigerant number (R-number) R-410-A / natural gas 7. British Thermal Unit (BTU) heating output rate: 130,000 B. New Equipment Specifications: 1. 8.5 Ton Units 2. 80 percent (80%) or better natural gas furnaces 3. British Thermal Unit (BTU) heating output rate equal to or better than current equipment 4. Stainless steel heat exchanger 5. 15.57 Seasonal Energy Efficiency Ratio (SEER) or better cooling system with hail guards 6. Plenum and/or Transition will be metal and fully insulated. 7. New HVAC units, reference model: Carrier model 48FCSM09A2A5-0A0A0 WeatherMaker Rooftop Unit or Lennox model LGX102S5-PKG 8.5 Ton Packaged Gas/Electric Unit 230 Volt /3 Phase /60 Hertz 454B Stainless Steel Heat Exchanger Rooftop Unit or equivalent or better. C.3 STATEMENT OF WORK C.3.1 Requirements: A. Removal of Existing Lennox manufactured 8.5-Ton HVAC Units. 1. Contractor shall coordinate with the TMD Project Manager (See Page 15 for Project Manager contact information) and TMD will provide a staging area to place equipment and existing units once removed from the building. 2. Contractor shall be responsible to provide all required tools and equipment for the proper disconnection and removal of the existing HVAC systems. 3. Contractor shall disconnect existing gas line from units 4. Contractor shall disconnect existing electrical lines from units and will follow lockout and tagout procedures of disconnecting electricity 5. Contractor shall remove the existing Lennox manufactured 8.5-Ton units from their current location and properly move the unit to the indicated contractor staging area on property.