A. System No. One Requirements: Contractor must replace corroded T-type fittings and elbows on various sprinkler pipes in mechanical rooms 21, 205 and 253A. B. System No. Two Requirements: 1. Contractor must replace packing on one (1) fire pump. a. Manufacture: SPP Pumps Inc. or approved equal. b. Serial number: USF-01-09-1242. c. Pump Type: PC06G 2. Contractor must replace two (2) fire hydrants, 173-5 ¼, 200 Cold Work Pressure (CWP). Fort Bliss requirement: Manufacturer Kennedy. 3. Contractor must conduct five (5) hydrostatic testing on pipes to the sprinkler system. 4. Contractor must test the Fire Department Connection (FDC) for hydrostatic testing. C. System No. Three Requirements: 1. Contractor must evaluate and repair (or replace) fifteen (15) overhead rolling fire doors covering windows on the second floor that do not work. 2. Contractor must evaluate and repair (or replace) six (6) overhead rolling fire doors covering six (6) bays that lead into the main hallway. 3. Contractor must evaluate and repair (or replace) three (3) overhead rolling fire doors cover windows in the assembly hall do not work...