Test Supervisory Signal Devices (pressure, water, temp.) Quarterly EP 1 NFPA 72 -2010: Table 14.4.5 Test all supervisory devices (e.g., pressure switches). Test Valve Supervisory Switches Quarterly EP 2 NFPA 72-2010: Table 14.4.5; NFPA 25-2011: Table 5.1.1.2 Ensure valve switches are functional. Additional Testing per FM request. Test Smoke Detectors, Heat Detectors, Manual Boxes Annually EP 3 NFPA 72 - 2010: Table 14.4.5 Test for proper operation and response. Test Visual & Audible Fire Alarms Annually EP 4 NFPA 72 - 2010: Table 14.4.5 Ensure clear visual and audible signals. Test Fire Alarm Communication for Off-site Notifiers Quarterly EP 5 NFPA 72-2010: Table 14.4.5 Test communication with monitoring service. Additional Testing per FM request. Test automatic smoke-detection shutdown devices Annually EP 19 NFPA 90A-2012: 6.4.1. Test automatic smoke-detection shutdown devices for air-handling equipment. Sprinkler System Inspection Grid (Aligned with TJC EC.02.03.05) Inspection Item Frequency TJC EC.02.03.05 EP NFPA Reference Inspector Comments/Findings Test Main Drains at Low Points Quarterly EP 9 NFPA 25-2011: 13.2.5 Test to ensure proper drainage. Additional Testing per FM request. Inspect Fire Department Water Supply Connections Quarterly EP 10 NFPA 25-2011: 13.7 Check for obstructions and functionality. Test Fire Pumps Under Flow Conditions Annually EP 11 NFPA 25-2011: 8.3.3 Test system flow and pump operation. Hydrostatic Test for Standpipe Systems Every 5 Years EP 12 NFPA 25-2011: 6.3.1, Table 6.1.1.2 Test water flow and pressure.