Specifications include, but are not limited to: 1. Ductile or Cast Iron: Pipe and Miscellaneous Fabrications Interior, Non-Immersion Surface Preparation: Surface shall be clean and dry. Remove Black Coating in accordance with NAPF 500‐03‐04. Portions of piping are believed to be lead based. See lead remediation section. 1st Coat: 161‐Color Tneme Fastcure at 4.0 ‐ 6.0 mils DFT. 2nd Coat: 161‐Color Tneme Fastcure at 4.0 ‐ 6.0 mils DFT. 3rd Coat: 161‐Color Tneme Fastcure at 4.0 ‐ 6.0 mils DFT. 2. Steel Pipe, Supports and Miscellaneous Fabrications Interior, Non-Immersion Surface Preparation: SSPC‐SP6 Commercial Blast Cleaning to achieve a minimum uniform angular profile of 1.5 mils. See lead testing results for concentration levels and the necessity of remediation. 1st Coat: 161‐Color Tneme Fastcure at 4.0 ‐ 6.0 mils DFT. 2nd Coat: 161‐Color Tneme Fastcure at 4.0 ‐ 6.0 mils DFT. Minimum 8.0 mils shall be applied to all surfaces. 3. Interior: Room E Ceiling Surface Preparation: Remove all coatings by suitable means including but not limited to abrasive blasting, vapor blasting, high pressure water, grinding. Prepare per SSPC SP-13 / ICRI CSP 2-3. Owner testing of current coatings result as lead-based. Reference lead section for remediation requirements. Filler (As Required): Fill flush all bug holes and voids with Series 215 Epoxy Surfacer. Deeper voids can be bulked with sand per manufacturers recommendations. 1st Coat: Tnemec Series 113 satin / Series 114 gloss – color H. B. Tneme Tuffcoat at 4.0 – 6.0 mils DFT. 2nd Coat: Tnemec Series 113 satin / Series 114 gloss ‐ 02WH Iceberg White H. B. Tneme Tuffcoat at 4.0 – 6.0 mils DFT.