Specifications include, but are not limited to: Quantity: 1 – 102KW generator with automatic transfer switch ____________________ Make: Please specify ____________________ Model: Please specify ____________________ The generator set shall be Standby Duty rated for the specified KW rating ____________________ The generator set shall be 102 KW STANDBY RATED, with an alternator rated for a Class B 80°C temperature rise or Class F 105°C temperature rise CONTINUOUS. It shall provide 128 KVA and 102 KW when operating at 240 volts, 3Ø 60 Hz, 0.80 power factor STANDBY. The generator set shall be capable of a 130°C STANDBY rating while operating in an ambient condition of less than or equal to 104°F and a maximum elevation of 1600 feet above sea level. The standby rating shall be available for the duration of the outage.