• Provide (1) one new 4-ton packaged unit that meets the following specifications: o 14.3 SEER heat pump packaged unit with rooftop curb adapter o Balance outside air to 160 cfm o Equip with 9kw electric heat kit • Install new 60 amp 208/3V (3#6, 1#10G, 1”C) circuit to existing panel board • Removal and disposal of the existing unit. • Provide any required piping, valves, and electrical installation, including new insulation and heat tracing for the outdoor CHW piping, if necessary. • Provide tie-in to the building’s existing BAS system costs to be included, if necessary. • Any crane rental and trucking costs shall be included. • Assume the use of the owner’s dumpster for the disposal of everyday construction trash. Any big items shall be hauled off by the vendor. • Respondent shall list warranty information and an approximate lead time on their bid submittal. • Respondent shall be responsible for properly installing units onto the roof and ensuring proper fit as part of the total cost, including any necessary roofing work. • Payment and Performance Bond will be required if the bid is $100,000 or over. • Respondent to provide total costs, including all parts, materials, and labor required to complete the project. All labor should be based on normal working hours. • Respondent to also provide a breakdown of pricing if the owner purchases the unit directly using the county’s tax-exempt status – reflect what the amounts will be for the unit to be purchased directly by the county. Sumner County reserves the right to purchase the unit directly. • The awarded vendor will be responsible for ensuring all applicable code requirements are met.