Specifications include, but are not limited to: The Contractor shall design and build a system which will enable all campus buildings at each location identified in the RFP to meet current International Fire Code (IFC) 510 Requirements and increase signal strength for the following (where applicable): •York County Department of Public Safety Communications ‐ 800 MHz radio system; •South Carolina “Palmetto 800” MHz radio system; The scope of this project includes all design, development, coding (if needed), licensing (if required), procurement and delivery of ERRCSs, associated amplifiers, antennas, cabling, power, and uninterrupted power supplies (UPS), testing, lightning protection, dedicated monitoring/annunciator panel, and cost of installation to achieve 95% coverage; • Westell Public Safety 700/800MHz 90dB, CLASS A, Bi‐directional Distributed Antenna with monitoring (or equal).; • EMR 12-hour backup battery (or equal).; • LMR 400LLPL Coax for horizontal installations (or equal).; • Connectors for LMR 400‐LLPL (or equal).; • PolyPhaser.; • Lightning Protection kit (or equal).; • Terrawave public safety ceiling antennas (or equal).; A. All equipment shall be new and be Federal Communication Commission (FCC) approved.; B. ERRCSs are installed in safe and easily accessible locations.; C. The system meets current radio system (700/800 MHz) requirements.; D. Installation complies with all national and/or local building, fire and electrical codes which pertain to signal, power, cable installations, grounding or enclosures as appropriate.; E. UPS installed can maintain ERRCS at full functionality for a minimum of 12 hours.; F. All software and licensing requirements and associated expenses are included.; G. Close coordination of project tasks and resources with the School District.; H. Documentation of complete testing for each ERRCS and UPS to ensure functionality and coverage for the building is at a minimum 95%.; I. All installations shall be completed by the timeline proposed by the Contractor for each location.; J. Coordinate ERRCS activation and testing with donor system licensee(s).; K. Complete any registration and frequency coordination with the FCC, donor system licensee(s), and others as required by applicable regulations or requirements.