Specifications include, but are not limited to: Provide and Install new/replacing the existing 480 volt Panel with new SQD 480 volt 225amp Rated panel to containing the (14) 30amp 3phase beakers Provide and Install the (14) 3 phase 480 volt receptacles on a dedicated circuit Provide and Install (12) 120 volt 20 amp receptacles in wall and in the existing wire mold for lab tables Provide and install in place of the existing 40amp panel feed a 200amp 3 phase feeder from the electrical room to the existing location. Provide and Install all conduit and wire for scope above Painting of work area from the conduits to mechanical room Provide SQ D items to include: 200 amp Rated Panel, Can and cover 480volt 15 3phase 15 amp 480 breakers 150 amp 3 phase 480volt sub feed breaker and sub feed lug kit All receptacles to be on a dedicated circuit. Independent third party testing Patching and/or painting of existing fireproofing if needed Short circuit, coordination and arc flash analysis if needed Offer must have a current mechanical contractor license