600 KWE Diesel Generator with a Tier 2 EPA rating 480/277V 3Phase 60HZ Supply automatic voltage regulator with PGM Excitation Control panel with emergency stop button and RS-485 communications to go to a remote annunciator. Must include all safety shutdown protection systems Enclosure should be Level 1 weatherproof with lockable doors and vibration suppression pads Mainline breaker 1000-amp 3 pole 600 volt breaker wired and mounted in Nema 1 enclosure Should include Engine block heater 5000w 240 vac CPJ series silencer Fuel tank should be 24/hour 1000-gallon Sub-based diesel fuel tank, double wall construction. Include fuel gauge, fuel leak switch and fill/ vent plumbing New ATS will be install on exterior of the building and have a 1200 amp fused disconnect. It should have a Nema 3R secure enclosure A new concrete pad for the generator is required Owner will clear the generator site and provide fuel after installation Start up and test after installation Warranty should be a minimum of 2 years or 2000 hours Contractor will be responsible for utility locate