Specifications include, but are not limited to: MacDougall Cafeteria Daikin AHU-1 208v/3ph CFM: 950 External Static Pressure: 0.5" Cooling BTUs: 44,100 Heating BTUs: 50,400 Salient Factor: AHUs must be delivered within 7 weeks Salient Factor: AHUs must fit existing equipment pads AHUs to include: High pressure steam preheat coils Chilled water coils Stainless steel drain pans ABB VFDs for balancing Mounted Disconnect Spring isolated fans (1) set of MERV 8 filters Hinged access doors for unit maintenance. ; MacDougall Cafeteria Daikin AHU-2 208v/3ph CFM: 11,111 External Static Pressure: 0.5" Cooling BTUs: 561,560 Heating BTUs: 428,000 Salient Factor: AHUs must be delivered within 7 weeks Salient Factor: AHUs must fit existing equipment pads AHUs to include: High pressure steam preheat coils Chilled water coils Stainless steel drain pans ABB VFDs for balancing Mounted Disconnect Spring isolated fans (1) set of MERV 8 filters Hinged access doors for unit maintenance.