Specifications include, but are not limited to: Minimum Chiller Effciency: ERR: 10.61 and IPLV: 15.73 460v/3ph Entering Water Temp: 54°F and Leaving Water Temp: 44°F Salient Factor: Chiller cannot exceed existing pad footprint of 88 [in] wide by 150 [in] Length. Stamped Structural Engineer drawing and concrete bill of material and labor costs must be included in price by vendor if chiller exceeds pad footprint. Salient Factor: Chill water lines must enter the chiller on left side when facing the electrical panels on chiller. Thermal dispersion flow switch and strainer — factory mounted Vibration isolation Shipping Weight: 4,500 lbs Required Low ambient operation to (-10)°F Single point power disconnect switch with circuit protection