Specifications include, but are not limited to: 41 Ton Daikin Air Cooled Chiller TAG: Canteen chiller Minimum chiller efficiency: EER: 11.9 and IPLV: 18.5 460v/3ph Entering water temp: 54deg F. and leaving water temp: 44deg F. Salient Factor: Chiller cannot exceed existing pad footprint of 88in. wide by 94in. length. Stamped structural engineer drawing and concrete bill of material and labor costs must be included in price by vendor if chiller exceeds pad footprint. Salient Factor: Chill water lines must enter the chiller on left side when facing the electrical panel on chiller. Painted exterior louvered hail guards factory mounted Thermal dispersion flow switch and strainer – factory mounted Vibration isolation Hot gas bypass Shipping weight: 2,964lbs Required low ambient operation to -10deg F Single point power disconnect switch with circuit protection 115v conscience outlet factory mounted Factory service start up.