Specifications include, but are not limited to: Fixture and lamp products must have DLC premium listing and eligible for National Grid incentives. Performance must be equal or superior to products listed in Table 1. Must have a minimum output of 125 lumen/watt or higher. Color temperature and color consistency - Color temperature must fall within a 7-step Macadam ellipse of the 3000K or 5000K points to ensure less color variation and a more uniform visible color for each color temperature, per the ENERGY STAR standard. Color rendering- CRI ≥80 with an R9>50 to ensure better representation of colors. Dimmability- Must be flicker and noise-free from 10-100% of driver output, per the ENERGY STAR standard. Rated life/warranty- All fixtures must comply with ENERGY STAR minimum lamp life requirements. Lamps and fixtures must carry a one-year parts and labor warranty, and a minimum five to seven-year free-replacement warranty. Light distribution- Omnidirectional and spotlights must meet ENERGY STAR distribution requirements. Testing Process - The testing process and requirements of lighting products purchased for this project are to meet applicable ENERGY STAR and DLC requirements. All lighting fixtures shall be furnished complete with mounting accessories to suit the specific service intended. Fixtures that are recessed shall be complete with any accessories required to fit the fixture to the ceiling/soffit construction.