Specifications include, but are not limited to: Provide granular activated carbon for the odor control system at T. F. Green International Airport Glycol Storage and Treatment Facility, located in Warwick, RI. The Rhode Island Airport Corporation (RIAC) is seeking bids for carbon media for two (2) odor control systems. The systems serve the Deicing Management System Tanks (DMTs) used to store collected spent aircraft deicing fluid. The primary parameter of concern is H2S. ODOR CONTROL VESSEL Manufacturer: ECS Environmental Solutions Quantity: Two each per tank (total of four) Model: V1-PAS 722 Carbon Adsorber Construction: Polypropylene (PPL) Configuration: Flat Bottom Vessel Diameter: 3 feet Removable Top (Lockable removable canister top) Bed depth: 34” Media Support: 1-1/2” mesh x 1-1/2” thick corrosion resistant FRP grating with perforated corrosion resistant polypropylene carbon retaining screen. MEDIA DETAILS The carbon media supplied shall be a vapor phase type, suitable for sewage system odor control. It shall have the following properties: Minimum H2S Breakthrough Capacity: 0.30 g H2S removed per cc of carbon Maximum Moisture: 5% by weight Apparent Density: 0.43 – 0.52 g/cc Minimum Carbon Tetrachloride Activity: 60% Minimum Hardness Number: 95 Maximum Ash Content: 5% by weight