A. List of Equipment to be serviced (SIEMENS data) Description Serial # Part # Sales Order Equipment # Qty 200hp Gen4 Drive PTVFD13236 A5E02788114 3002546651 40992506 1 300hp Gen4 Drive PTVFD13237 A5E02788105 3002546650 40992500 1 300hp Gen4 Drive PTVFD13238 A5E02788107 3002546650 40992501 1 200hp Gen4 Drive PTVFD13235 A5E02788103 3002546650 40992504 1 B. Preventive Maintenance Program 1. Vendor shall perform semi-annual Preventive Maintenance for NBC four (4) MV SIEMENS VFD per the following scope. a. Vendor shall monitor units’ current operating condition by viewing input and output voltage through the units existing Power Transformers (PTs), power supplies and speed reference with oscilloscope in the low voltage section of the VFD. This includes using oscilloscope and reading input and output voltages at the potential transformers inside the low voltage section of the VFD and recording any abnormalities. b. Vendor shall perform visual inspection and report on installation and environment and make corrections and/or recommendations where applicable. 1. Check for hot spots on all heat generating components and connection points 2. Check input and output terminals for discoloration 3. Check all wire condition and connections, secure and retorque if necessary 4. Verify that there is no foreign material (dust, metal, bolts, etc.) inside the cabinets 5. Vacuum the cabinet as required and clean/replace air filters