Specifications include, but are not limited to: 2. Shut down the existing electrical and gas service to the existing single zone Trane model SFHFC75 DX cooling and natural gas heating air handler, and controls on the east side of K building serving the offender housing area. 3. Decommissioning, dismantle and disposal of 1 existing Trane Air Handler with associated ducting and accessories 4. Disconnect and reconnect all utilities per code. 5. The air handler is located where an overhead covers the entire length and width of the unit along with support steel I-beam columns facing the outside and any newly installed air handler will be required to be pulled or rolled into position 6. Supply, install, test and commission 1-new, single zone DX cooling and natural gas heating similar to York model YPAL075MVE46, Vertical upward discharge, nominal 75 Ton, modulating gas heat, 460V, 3PH, 60HZ, 32,000 CFM Air Handler at 4.0 Total S.P. discharge pressure and a 1.0 Total S.P. return fan pressure, with associated ductwork, dampers and accessories. Design air moving equipment for site elevation ~500 ft.