Specifications include, but are not limited to:The contract for RFP-09-15 Replacement of HVAC System in EOC Building Data Room To schedule a site review please contact Steve Christian 903-590-4760 Two (2) Liebert Model BU067ADADEI025D Challenger 3000 Environmental Control System: Nominal 5 Ton-067 KBTU/H – Upflow Distribution System, 208-230 Volts 3Phase 60Hz Air Cooled Unit One digital scroll compressor with uploading solenoid valve System Accessories Liebert iCOM microprocessor with Large Graphic Display Display Language is English vNSA8 network switch; Qty 1 Factory Balanced Evaporator Motor & Blower Package The Liebert lntelliSlot Unity Card (IS-UNITY-DP) provides ground fault isolated RS-485 Modbus, BACnet IP and Modbus IP network connectivity to Building Management Systems for unit monitoring and management. Also, provides ground fault isolated 10/100 baseT Ethernet connectivity for unit monitoring and management. The supported management interfaces include: SNMP for Network Management Systems, HTIP for web page viewing, SMTP for email, and SMS for mobile messaging. This card can support dual IP and 485 protocols simultaneous. IS-UNITY-DP card is factory-installed in an lntelliSlot. This card can support dual IP and 485 protocols simultaneous. IS-UNITY-DP card isfactory-installed in an lntelliSlot. Electric Reheat Infrared w/ AutoFlush Humidifier Locking Disconnect (65kA SCCR) Qty-2 LT460-Z30, Zone Leak Detection Kit w/30 Foot Cable Condensate Pump - Dual Float 2" (5cm) MERV 8 Filter Package 2 HP Motor Smoke Sensor High Temp Sensor Compressor Crankcase Heater Unit Color : Z-0420