Specifications include, but are not limited to: Provide all equipment, labor and materials to remove and legally dispose of Eight (8) RTU HVAC units and install Eight (8) AAON RTU HVAC units at The Woodlands Township Town Hall. Qty (7) High Efficiency, Vertical Airflow, Gas Heating, Air-Cooled Packaged Rooftop Units, designed for 460V/3Ph/60Hz power, and Complete as follows: Unit Construction and Description: • G90 Galvanized Steel Casing with Enamel Finish Withstanding 2,500 Hour Salt Spray per ASTM B117-95 • Unit Cabinet is Thermally Broken Double Wall Construction with 2” Thick, R-13 Foam Insulated Panels • Access Doors with Full Length Stainless Steel Piano Hinges and Quarter Turn, Zinc Cast Lockable Handles • Digital Scroll Compressors • Metal Mesh Pre-Filter + 2” 30% Filters (one Set) • #304 Stainless Steel Sloped Drain Pan • Supply Fan Configuration: Direct Drive Backward Curved Plenum Fan + Premium Efficiency ODP Motor + Variable Frequency Drive • Al/Cu Condenser Coil • 115V Convenience Outlet (Factory Wired) • SA Smoke Detector • ETL U.S.A. Listing • Flat Curb Adapter as required to utilize existing ductwork