Specifications include, but are not limited to: Provide services related to a full HVAC replacement in the 1st Floor South in Price building. furnish all labor, materials, equipment, tools, facilities, supplies, and services and do all things necessary for the project to be successfully completed. Construction: 1. Open drip-proof type except where specifically noted otherwise. 2. Design for continuous operation in 40 degrees C environment. 3. Design for temperature rise in accordance with NEMA MG 1 limits for insulation class, service factor, and motor enclosure type. 4. Motors with frame sizes 254T and larger: Premium Efficiency Type. . Wiring Terminations: 1. Provide terminal lugs to match branch circuit conductor quantities, sizes, and materials indicated. Enclose terminal lugs in terminal box sized to NFPA 70, threaded for conduit. 2. For fractional horsepower motors where connection is made directly, provide conduit connection in end frame.