The City is seeking generators from the following manufacturers, or equivalent: Cummins, CAT, and MTU. The City reserves the right to determine what qualifies as an equivalent. Due to funding requirements, all equipment must be received and installed by June 1st; please bid only on items that you will be able to both deliver and complete the installation by that deadline. Include with your bid the delivery timeline for each generator. All components of the generator must be able to operate under extreme heat, more than 110 °F. The City requests that all generators be backed by a comprehensive 5-year warranty and prefers that generators be backed by a national or worldwide distributor. Generators and exhaust discharge must be compliant with all applicable local, state and federal codes and standards. Listed below are the necessary components needed for each location: City Hall Annex (Voltage: 480v 3 phase): • 250 KW Natural Gas Generator with OmniMetrix generator monitoring or approved equal that is compatible with all manufacturers • ATS 600A Service Entrance Rated • Installation of Generator Foundation and Electrical • Electrical Material, Copper Wiring, Conduit • Enclosure rated at NEMA 3 or 4, minimum 150mph & 70dba • Crane to Lift, Transport, and Place Generator • Separate disconnect built into ATS outdoor cabinet enclosure • Megohmmeter testing of existing wires • Removal/disposal of existing generator & transfer switch • Training • Delivery (include price, if any, & delivery time) • 5-year Warranty Civic Center (Voltage: 120/208 3 phase): • 125 KW Natural Gas Generator with OmniMetrix generator monitoring or approved equal that is compatible with all manufacturers • ATS 600A Service Entrance Rated • Installation of Generator Foundation & Electrical & Regulator • Electrical Material, Copper Wiring, Conduit • Separate disconnect built into ATS outdoor cabinet enclosure • Enclosure rated at NEMA 3 or 4, minimum 150mph & 70dba • Crane to Lift, Transport, and Place Generator • Training • Delivery (include price, if any, & delivery time) • 5-year Warranty Public Works Operations Center (Voltage: 480v 3 phase): • 200 KW Natural Gas Generator with OmniMetrix generator monitoring or approved equal that is compatible with all manufacturers • ATS 600A Service Entrance Rated • Installation of Generator Foundation & Electrical • Electrical Material, Copper Wiring, Conduit • Separate disconnect built into ATS outdoor cabinet enclosure • Enclosure rated at NEMA 3 or 4, minimum 150mph & 70dba • Crane to Lift, Transport, and Place Generator • Megohmmeter testing of existing wires • Training • Removal/Disposal of Existing Generator • Delivery (include price, if any, & delivery time) • 5-year Warranty Community Center (not a registered historic building; Voltage: 480v 3 phase): • 200 KW Natural Gas Generator with OmniMetrix generator monitoring or approved equal that is compatible with all manufacturers • ATS 400A Service Entrance Rated • Install Generator Foundation • Electrical Material, Copper Wiring, Conduit • Install Electrical • Separate disconnect built into ATS outdoor cabinet enclosure • Enclosure rated at NEMA 3 or 4, minimum 150mph & 70dba • Crane to Lift, Transport, and Place Generator • Training • Delivery (include price, if any, & delivery time) • 5-year Warranty