Provide, install and start-up one (1) fan coil unit a. The Contractor shall provide and install one (1) ENVIRO-TEC HPE14, 55,449 BTU Total Cooling Fan Coil Unit, Front Supply Grille, Rear Return Grille and accessories or approved equal. Remove the existing fan coil unit and accessories and recycle them through a recycling center or equivalent recycling method. b. Fan Coil Specifications: 1. Voltage: 120 VAC. 2. Phase: 1. 3. Enclosure: UL Type NEMA 1 (indoor). 4. FLA 9.6. 5. AIRFLOW 1,337 CFM. 6. CHW Flow Rate 11.3 GPM. 7. LAR: 54.5*F DB/53.7* WB. 8. EAT: 80*F DB/67* WB. 9. EWT/LWT: 45*F DB/55.1*F. 10. FPD: 7.4 (FT.WG). 11. ESP: 0.05 (IN.WG). 12. ROW: 6. 13. Coil Connection Size: 1-1/8” inch. 14. Filter: 2” inch, 30% Pleated (Merv 8).