Annual Inspection and Testing 8.2.1.1 Inspect generator circuit breaker for signs of wear, damage, or overheating. Tighten all electrical connections to manufacturerrecommended torque specifications. 8.2.1.2 Inspect and clean the engine/generator control panel and connection panel, removing dust, debris, and corrosion as needed to ensure reliable operation. 8.2.1.3 Inspect and service the Automatic Transfer Switches (ATS), including its enclosure, for cleanliness, integrity, and proper mechanical function. 8.2.1.4 Verify proper operation and timing of the ATS and associated control systems, including transfer and retransfer sequences, time delays, and signal responsiveness. 8.2.2 Resistive Load Bank and Test 8.2.2.1 The generator will be placed on a resistive load bank capable of providing a load at 100% nameplate rating of the generator unit. This load will be supplied for a minimum of 2 hours. During the load test, all displayable operating parameters will be monitored and logged...