• Perform one (1) functional fire alarm system tests per building listed in Section 7.0. • Perform two (2) Sensitivity test per building listed in Section 7.0. • A 100% sensitivity test shall be performed, in addition to the functional test, in the second year of the contract on all buildings listed in Section 7.0. • Smoke/heat detectors shall be tested as per NFPA 72, 2019, or the latest edition. • Smoke/heat detectors were found to have a sensitivity of 0.25 percent/ft. Obscuration or more outside the listed and marked sensitivity shall be cleaned and recalibrated. • After each test, the successful bidder shall submit a handwritten or printed copy of each test's results to the requesting department’s designee. • Within five (5) working days after the completion of each test, a typewritten report shall be submitted to the requesting department listing the results of each test and a detailed list of all deficiencies found at the time of each test. • Under a separate purchase order, Jefferson Parish will be responsible for repairing all deficiencies found. • Within ten (10) days of notification from Jefferson Parish, the successful bidder shall perform an inspection on all repaired devices. • The second inspection shall be performed at no additional cost to Jefferson Parish. • After all inspections are performed and all deficiencies repaired, the successful bidder shall properly tag the system as per NFPA guidelines.