1. Core Model #30NFR HazMat Storage Building or equivalent 2. Walk in storage building with 3 equal compartments 3. Exterior Dimensions shall be a minimum size of 6’ Wide X 30’ Long X 8’ Height 4. Walls and Roof: Single-wall 12 gaugesteel welded construction, non-fire rated 5. Sump: Each compartment shall have a 240-gallon sump, 10 Gauge Steel Welded Construction, for spill containment, located beneath aluminum grate floors 6. Floor: Aluminum bar grating and minimum load rating of 300 lbs/ft2 7. Compartments: Three equal bay compartments divided by single-skin steel walls with full opening doors on each bay for pallet access 8. Forklift pockets: Standard base lifting points 9. Fire Protection: Gravity-closing fire dampers on each air vent 10. Ventillation: 12” gravity vents with spark arrestors. Shall include PVC vent stack extensions. 11. Grounding: Static ground rof and grounding lugs 12. Drainage: Common external drain port for manual sump evacuation 13. Shall have nine steel shelves, with 3 in each compartment placed on the left, right, and back walls. 14. Shall have 2 steel loading ramps (36” x 60”) 15. Shall have three Explosion Proof Lights (Class I, Div I) with one light per compartment and switch for each compartment 16. Shall have Dry Chemical Fire Suppression System with Steel Enclosure (UL & FM Approved) 17. Shall contain a 10lb fire extinguisher in each compartment 18. Shall have (6) Doors (56" X 82") with (3) Point Locks 19. Shall have NFPA Signs. 20. Shall unload and set building on poured concrete pad 21. Shall anchor building to concrete pad