A. Provide factory-assembled, wired, and tested outdoor air-cooled liquid chiller consisting of screw or scroll compressors, air-cooled condenser, evaporator, expansion valve, refrigeration accessories, variable frequency drives/starters, and control panel. B. Control panels, structural elements, electrical boxes, and heavy-gauge structural base shall be constructed of heavy-gauge structural steel with weather-resistant baked-on enamel powder or prepainted prior to assembly. C. Chiller performance requirements are summarized below. See Bid Form for additional requirements. Refrigeration capacity: 139 tons; Approximate footprint*: See Exhibit 2; Existing operating weight**: 11,077 lbs.; Motor voltage: 200/3/60; Existing MCA: 665 amps; Existing breaker size: 1000 amps; Full load power consumption: As rated; Full load performance: 10.1 EER (Path A) / 9.7 EER (Path B); Part load performance: 13.7 EER (Path A) / 15.8 EER (Path B)...