SCDC is soliciting to obtain the following: Blue Star PD200 Diesel General w/ 72-hour (1125-gallon tank) or Equivalent; ASCO 300 Series 400 Amp Transfer Switch 277/480V 3PH Nema 1; SCDC will provide concrete pad for generator. SCDC will fuel generator prior to start up. This will be a Turnkey Procurement. SPECIFICATIONS; 200 kW Diesel Generator ; Blue Star Model PD200 or Equivalent; Fuel System: Diesel; Engine Model: Perkins 1106D-E70TAG5 200kW Standby Power Rating at 1800RPM – Governor – Electronic Isochronous; Voltage: 480/277V 3 Phase 60 Hz 0.8 PF; Gen Model: Stamford UCI274H 12 Lead Wired 480V 3 Phase High Wye 125°C Rise Over 40°C Ambient; Voltage Regulator: Stamford AS440 Automatic Voltage Regulator; Control Panel: Blue Star DCP7310 Microprocessor Based Gen-Set Controller Mounted Facing Left from Generator End (Unless Specified Otherwise) Standard Emergency Features: Low Oil Pressure, High Coolant Temp, Overspeed, Overcrank Shutdowns Stop Pushbutton, Audible Alarm Buzzer with Silencing Switch; Control Panel Options: Low Water Level Sensor with Shutdown Break Glass E-Stop Station - Send Loose; Remote Annunciator: Deep Sea DSE2548 (2x) Remote Annunciator with Enclosure (Surface Mounted); Unit Color: Gray; Enclosure: Level 2 (Weather Proof Enclosure with Foam) Powder Coated 14 Gauge Steel Rugged and Durable 200 MPH Wind Rated Enclosure Pitched Roof for Increased Structural Integrity and Improved Watershed Punched Intake with Baffle and Punched Exhaust Openings Keyed Alike Lockable Doors with Draw Down Latches and Stainless Steel Component Hinges Additional 1.5" Thick Polydamp Type D Acoustical Foam (PAF) Formed Steel Base with Mounting and Lifting Holes Includes Vibration Mounts to Isolate Unit from Base Rail Sound Attenuation Foam: Sound Attenuation Installed in Enclosure; Cooling: Unit Mounted Radiator (50°C Ambient); Oil Drain Extension: Plumbed to Bulkhead Fitting in Base; Mainline Breaker: : 300 Amp 3 Pole 600 Volt Breaker Mounted & Wired in a NEMA 1 Enclosure; Jacket Water Heater: Engine Block Heater 2000W 240VAC Rated for -20°F Heater Installed with Isolation Valves and Wired to Terminal; Air Cleaner: Dry Single Stage; Air Restrictor Indicator: Installed Air Filtration System; Silencer: Critical Grade Compact (CPJ Series) Silencer Mounted to Engine ; Battery: 12 Volt System with Racks & Cables; Battery Charger: DSE 12 Volt 10 Amp Mounted and Wired to Terminal ; Fuel Tank: 72 Hour 1125 Gallon 142 Listed Sub-Base Fuel Tank with Stub-up Area Double Wall Construction with Secondary Containment Standard – Includes: Supply and Return connections, Fuel Level Guage, Fuel Leak Switch and Fill Vent Plumbing; Factory Test: Standard Commercial Testing Includes: Verification of Alarm Shutdowns, Voltage Settings, Block Loading to Rated kWe and F degree. Warranty: 5-year