The St. Johns River Water Management District’s (District) Bureau of Water Resource Information is dedicated to collecting groundwater quality data throughout the 18 counties in the District. The District will be installing dedicated submersible pumps in some of the groundwater quality monitoring wells. Required minimum specifications: GEOFLO 3 (22S10) Supply Voltage: 1x200-240V +6%/-10% 50/60 Hz PE 1 x100-115V Operation via Generator: As a minimum the generator output must be equal to the motor P1[KW] +10% Starting Current: The motor starting current is equal to the highest value stated on the motor nameplate Minimum Ambient Temperature: 4°F (-15°C) Maximum Ambient Temperature: +104°F (40°C) Maximum Ambient Fluid Temperature - 86°F (°C) Liquid Temperature: The temperature of the pumped liquid should not exceed 104ºF (40°C). Starting: Soft-start Run-up Time: Maximum: 2 seconds Motor Protection: The motor is protected against: Dry running, overvoltage, undervoltage, overload, overtemperature Power Factor: PF=1 Service Factor: 0.33-0.50A[Hp]-1.75 at 11 5V/230V\n0.50-0.75B[Hp]-1.4 at 230V\n1. 0- 1.5C[Hp]-1.15 at 230V; REDIFLO 2 Full Load Rating - 5 HP / 220V / 3 PH / 400Hz / 5.5A Maximum Current (SFA) - 5.5 amps Motor Protection - Thermal overload - Thermik Geratebau, Series SY6 - (176°F [80°C]) Current Overload - Incorporated into Redi-Flo VFD (9.0A for 10 seconds) Discharge Port - 1/2" Female NPT Minimum Ambient Fluid Temperature -34°F (1°C) Maximum Ambient Fluid Temperature - 80°F (28°C) Motor Lubricating Fluid -Deionized (DI) Water Minimum Ambient Storage Temperature - 34°F (1°C) Maximum Ambient Temperature - 120°F (50°C) Dimensions - 11.3" length x 1.81" diameter Cooling Shroud, Stainless steel