1 Roots Model 412 RAM Rotary Lobe Positive Displacement Blower 1 Motor, 50 HP, TEFC, 1770 RPM, 480 V, 3 Phase, 60 Hz, IEEE 841 Inverter Ready 1 Yaskawa FP605 50 HP 480 Volt 3 Phase Model 4065AFA. Drive only. Will be placed in existing cabinet. Yaskawa is preferred brand for wastewater treatment plant VFD’s 1 V-Belt Drive System • Blower Bushing • Motor Bushing • Blower Sheave • Motor Sheave • Banded Belt, 3-5VX1150 (or approved equal) Approximately 60” Center Distance • V-Belt Drive Guard 1 6” x 6” EPDM Inlet Expansion Joint 1 6” x 6” EPDM Discharge Expansion Joint 1 Inlet Silencer, 6” Blower FLG – Custom Length Side Connection, SS 1 Discharge Silencer, 6” Blower FLG – Custom Length Side Connection, SS 2 Inlet Silencer Spool Piece, 6”FLG x 8” FLG to tie into existing pipe and gaskets, SS 1 Discharge Silencer Spool Piece, 6” FLG x 8” FLG to tie into existing pipe and gaskets, SS