The scope of work includes but not limited to the following: Furnish all labor, materials and equipment to perform all work described below in accordance with the construction drawings, locally adopted building code and other authorities having jurisdiction provide the following services. Electrical Rough-in: Provide rough-in electrical services to single family, duplex and multifamily (4-plex or less) as directed by CIHA Construction. All work is to be in accordance with the latest Municipal adopted (NEC) National Electric Code. CIHA Electrical Standard to include but not limited to: Appropriate code approved service entrance depending on the building type. Provide approved meter labels on multiple meter panels. 125 Amp distribution panel for each unit. Wire distribution to all boxes, outlets, switches, appliances, and heating equipment. Provide distribution to a crawlspace exhaust fan, and bathroom exhaust fans and make hot at rough-in phase (exhaust fans installed by others). Provide a 120 volt hardwired, interconnected smoke and carbon-monoxide detection system. The signaling devices shall be white in color. Outlets to code, include one on each exterior deck. Provide one (1) Dehumidistat in each crawlspace. Provide switched lighting rough-in for the lighting plan