The work includes construction of a level concrete pad, installation of generator on the pad, all electrical installation/connections, and all natural gas installation/connections. For the HMGP 4400-0066: NATURAL GAS/DIESEL FIXED COMMERICAL/INDUSTRIAL GRADE STANDBY GENERATORS, the following will note the general named locations and size of each generator at said location: o Lift Station 20 – 40kw generator, 120/240 V, 3-phase, natural gas/150 amp breaker ATS switch/200 amp 120/240 3-phase NEMA stainless steel/150 amp breaker with mobile cellular link o Lift Station 23 - 20kw generator 120/240, 3-phase, diesel/100 amp breaker ATS switch/100 amp,120/240 3-phase NEMA stainless steel/100 amp breaker with mobile cellular link o Lift Station 26 - 50kw generator, 120/240 V, 3-phase, natural gas/150 amp breaker ATS switch/200 amp 120/240 3-phase NEMA stainless steel/150 amp breaker with mobile cellular link...