National 10" - HH70 Discharge head with 1-1/2" stuffing box with stainless packing glands and bolts epoxy coated OD 120' of 10" x 1-1/2" x 0.365" wall column assembly - 416 SS shafting with 304 SS couplings, 316 SS retainer rings, 1-1/2" x 2-1/2" Run dry Poly and NSF approved bearings, fabricated column flange for 16" casing with two-1" SS ports and 1" transducer tubes to top of the bowl. National H14LC-2 stage bowl assembly, 2300 GPM @ 130' TDH, 316 SS dynamically balanced impellers, SS collets and bolting, epoxy coated OD, 316 SS 10" cone strainer, and bowl bearings to be poly/vesconite type NSF approved. Provide labor and equipment to install the pump, run discharge piping, flush the well until clear, CL2 the well and pump, let sit over night, and flush in prep for Bac-Ts. Run 6 hour step test, 3 steps at 75%, 100% and max with transducer recording the background data, test data, and recovery. Report of results and installation report required.