1. Perform visual inspection: Inspect the UPS solution to ensure that all system components are clean and function within designed specifications. 2. Perform environmental inspection: Verify and document that the system’s environment is within specified operating conditions including but not limited to room temperature, airflow, dust contamination, etc. 3. Perform mechanical/electrical inspection: Inspect all power and control wire termination points as well as all UPS system components. 4. Perform functional verification: a. Check UPS event and alarm logs. b. Verify that input, output, and bypass voltage current values are within designed specifications. c. Check parallel operation performance. 5. Implement updates: a. Verify and implement all required field advisories and field modifications. b. Check all circuit board revisions and update as required. 6. Check batteries (battery) life and replace batteries as needed. The price for batteries must be listed on Page 2 of the Bid Proposal.