Maintenance TB Terminal/Blower System All testing must be performed to federal standard. #209B IES-RP-CC-001-86 and/or manufactures specifications. Upon contacting the vendor, the vendor will have a 24-hour turn around to service the facility. There are four isolation rooms, each room has a primary filter and a pre filter. Services are to be performed three times per year. Services to include the following: 1. Filter replacement and blower maintenance for each of the four new isolation rooms, three times per year. 2. Supply and replace HEPA filters: * Primary filter(s): 24" X 24" X 11" * Primary filter(s): 12" X 12" X 24" * Pre filter(s): 24" X 24" X 11" 3. Recalibrate exhaust system. 4. Check duct for leaks & seal any leaks found. 5. Vendor to rebag, box up, and dispose of used filters off site. 6. Replace belt on the exhaust blower three times per year. 7. Adjust the blower operation to provide negative pressure in all isolation rooms served by the system. 8. Replace motors, drivers and parts as necessary to maintain the system in design condition. 9. Provide a report on the condition of the exhaust filtration system after completion of each service visit.